This chapter provides the technical data of the GMW90 series
transmitters.
Specifications
Table 14 Performance
+20 … +30 °C (+ 68 … + 86 °F)
± (30 ppm + 2 % of reading)
+10 ... +20 °C, +30 ... +40 °C
(+50 ... +68 °F, +86 ... +104 °F)
± (35 ppm + 2.7 % of reading)
-5 ... +10 °C, +40 ... +55°C
(+23 ... +50 °F, +104 ... +131 °F)
± (45 ppm + 3.8 % of reading)
Stability in typical HVAC applications
Total accuracy at room temperature
±75 ppm at 600 and 1000 ppm
-5 ... +55 °C (+23 ... +131 ºF)
+20 ... +30 °C (+68 ... +86 °F)
+10 ... +20 °C, +30 ... +40°C
(+50 ... +68 °F, +86 ... +104 °F)
-5 ... +10 °C, +40...+55°C
(+23 ... +50 °F, +104 ... +131 °F)
Digital temperature sensor
0 ... 95 %RH, non-condensing
Temperature range +10 ... +40 °C
(+50 ... +104 °F)
Temperature range -5 ... +10 °C,
+40 ... + 55 °C (+23 ... +50 °F,
Stability in typical HVAC applications
*Complies with CEC-400-2008-001-CMF