RFL100 does not implement the Alarm Delay and Alarm o margin settings of
viewLinc threshold alarms. Local alarm status on RFL100 changes as soon as the
measured values cross the thresholds.
2.6.1 Alarm examples
Figure 7 RFL100 with high alarm active on channel 1
Figure 8 RFL100 with high-high alarm active on channel 1
2.7
 Service port
The service port of the data logger provides a local interface for performing service actions
that cannot be done over the air, such as updating the device firmware. The service actions are
based on file transfer using Media Transfer Protocol (MTP), so no special software is needed.
The service port connector is a standard micro-USB connector.
The service port can be used to supply operating power to the data logger. Use a power
supply that fulfills the requirements listed in Table 8 (page 18).