10.5 Connecting an Entry and an Exit reader to ACT in Wiegand
mode
1. Entry reader
2. Exit reader
Connect Entry reader to ACTpro-15xx controller
Wire the connections between an Entry reader and an ACTpro-15xx controller as follows:
AB-+ Terminal block ACTpro 1520
A
DATA/D0
B
CLOCK/D1
-
0V/GND
+
+12/24 V
R Y/T G H Terminal block ACTpro-15xx
R
RED
Y/T
G
GREEN
H
Connect Exit reader to ACTpro-15xx controller
Wire the connections between an Exit reader and an ACTpro-15xx controller as follows:
AB-+ Terminal block ACTpro 1520
A
SENSE
B
CLOCK/D1
-
0V/GND
+
+12/24 V
© Vanderbilt 2021 37
A-100410-d
12.02.2021
Mullion Reader VR20 VR50 – Installation Manual Connecting VR20/VR50 readers to ACT