10.5.1 Set the jumpers for Wiegand mode
ENTRY reader EXIT reader
Jumper 1 OFF
Jumper 1 OFF
Jumper 2 ONtop 2 links (32-bit)
Jumper 2 ONtop 2 links (32-bit)
Jumper 3 OFF
Jumper 3 OFF
Cable length guide
Mode Max. Cable length Cable
Wiegand 30m.
Screened multicore (For
example; Belden 9538)
Mullion Reader VR20 VR50 – Installation Manual Connecting VR20/VR50 readers to ACT