Heat Pump Systems
You must enter an Installer Password to access the EQUIPMENT SETTINGS from the Main Menu.
The following settings can be changed for Heat Pump Systems:
DEFAULT OPTION
MIN ON/OFF TIME 3 MIN 1-6 MIN
Minimum cycle time for the heat pump/auxiliary heater.
ALLOW HP+AUX ON YES NO
Allows the Heat Pump and
Auxiliary Heat to be on at the
same time.
Does not allow Heat Pump and
Auxiliary Heat to be on at the same
time.
Control Options
You must enter an Installer Password to access the CONTROL menu from the Main Menu. The
following settings can be changed:
DEFAULT OPTION
CHANGE
HYSTERESIS
2
o
F (1
o
C)
0-6
o
F
(0-3
o
C)
Defines the number of degrees the temperature must pass prior to changing
from HEAT to COOL mode or vice versa in AUTO mode.
MAX RECOVERY
TIME
90 MIN 0 – 180 MIN
The maximum time the thermostat allows the equipment to reach a desired
temperature in 1
ST
stage heating (or cooling). If the thermostat determines
that the desired temperature will not be reached, it will engage the second
(or further) stage of heating (or cooling).