50
6 Set up with the display and adjustment module
FIBERTRAC 31 • Probus PA
43833-EN-170126
Setup
An address must be assigned to each Probus PA instrument. Each
address may only be assigned once in the Probus PA network. The
sensor is only recognized by the control system if the address is set
correctly.
When the instrument is shipped, address 126 is set. This address can
be used to test the function of the instrument and to connect it to a
Probus PA network. Then the address must be changed to integrate
additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
Hardware addressing is eective if an address less than 126 is set
with the address selection switches on the electronics module of
FIBERTRAC 31. In such case, software addressing has no eect -
only the set hardware address applies.
Software addressing is only eective if address 126 or higher is set
on the instrument with the address selection switches.
If a hardware address was adjusted (< 126), then the instrument
signals that the hardware address is active.
In this menu item you can assign an unambiguous name to the sen-
sor or measurement loop. Push the "OK" key to start the editing. With
the "+" key you change the sign and with the "->" key you jump to the
next position.
You can enter names with max. 19 characters. The character set
comprises:
•
Capital letters from A … Z
•
Numbers from 0 … 9
•
Special characters + - / _ blanks
In this menu item you can adjust the FIBERTRAC 31 to the isotope
installed in the source container.
Setup - Sensor address
Hardwar
e addressing
Software addressing
Setup - Measurement
loop name
Setup - Isotope