6 Set up with the display and adjustment module
FIBERTRAC 31 • Probus PA
43833-EN-170126
Menu Menu item Default value
Setup Sensor address 126
Measurement loop name Sensor
Isotope Cs-137
Application Limit level
Background radiation
0 ct/s
Temperature unit ° C
Adjustment mode 1-point
Adjustment (uncovered)
90000 ct/s
Delta I 90 %
AI FB1 Channel Process value
AI FB1 scaling unit %
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping 0 s
Mode relay Dry run protection
Lock adjustment Released
Display Language Selected language
Displayed value Pulse rate (ct/s)
With this function
Load parameter adjustment data from the sensor into the display
and adjustment module
Write parameter adjustment data from the display and adjustment
module into the sensor
The copied data are permanently saved in an EEPROM memory in
the display and adjustment module and remain there even in case of
a power failure. From there, they can be written into one or more sen-
sors or kept as backup for a possible sensor exchange.
Note:
Before the data are copied into the sensor, a check is carried out to
determine if the data t the sensor. If the data do not t, a fault signal
is triggered. When data are being written into the sensor, the display
shows which instrument type the data originate from and which TAG
number this sensor had.
Info
In this menu you will nd the following menu items:
Instrument name - shows instrument name and serial number
Additional settings - Copy
instrument settings