46 PCMS Operations, Safety & Maintenance V3.0 Ver-Mac 2018
12.8 Battery Bank Periodic Maintenance
Item
Function Required
Before
Each Use
3 Months
12 Months
Batteries
Battery Bank
Inspect outside of battery
(damage, cracking and leaking fluid)
Replace any leaking battery immediately
Inspect water level*
Fill as needed
Test with voltmeter
(fully charged 12.7 V or higher) Charge as
needed
Test with Hydrometer*. Check specific
gravity does not vary more than 0.05 units
between cells
Inspect terminals for corrosion, tightness of
connections
Clean as necessary
Boxes
Inspect for damage, water infiltration
Check that cover closes and locks securely
*Deep-charge batteries only.