No solar voltage reading on the controller
Serial communication defective or incorrectly
connected
Over voltage from batteries (greater than
15.15V)
Batteries incorrectly connected
Example: 12V batteries in series
Defective solar regulator (U101, Q102)
Battery voltage around
14.45V at -25°C
13.70V at 25°C
12.95V at 50°C
No solar voltage reading on the controller
Serial communication defective or incorrectly
connected
Controller displays solar voltage
(Example: 20.00V) but no solar current
One or more solar panels may be incorrectly
connected
Defective solar regulator (U101)
Solar current (entering current) is less
than the battery current (outgoing current)
Solar regulator is OK but there is not enough
sunlight
Check orientation of the solar array
Solar regulator is OK but the system is drawing
too much current
Solar current (entering current) is greater
than the battery current (outgoing current)
System OFF and no LEDs lit on regulator
Defective jumper switch or wire in J5
Fuse F2 blown
(F1 replacement fuse)
Ground disconnected
Check J2-2