MODEL NUMBER GXT3-5000RT208 GXT3-6000RT208 GXT3-8000RT208 GXT3-10000RT208
MODEL RATING 4000W/5000VA 4800W/6000VA 7200W/8000VA 9000W/10000VA
Bypass Protection Limits
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Operating Temp, °F (°C)
32 to 104 (0 to 40); see Operating temperature parameters on page 60
Storage Temp, °F (°C)
5 to 122 (-15 to 50)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating
Audible Noise
less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides
Agency
Safety UL 1778, c-UL Listed
RFI/EMI
FCC Part 15, Subpart B, Class A, FCC Class A
Surge Immunity
IEEE/ANSI C62.41 Category A & B
Transportation
ISTA Procedure 1A
MODEL NUMBER GXT3-6000RTL630
MODEL RATING 4200W/6000VA
Dimensions, Rack Mount, W X D X H, in. (mm)
Unit 16.9 x 22.6 x 8.5 (430 x 574 x 217)
Shipping 20.9 x 29.3 x 14.8 (530 x 745 x 377)
Weight, lb (kg)
Unit 51.8 (23.5)
Shipping 66.1 (30)
Input AC Parameters
Nominal Operating Frequency
Factory Default VAC
User Configurable VAC
208/220/230/240VAC
(may be modified with configuration program)
Table 12.2
UPS specifications—Liebert GXT3-6000RTL630