Technical data table
English
B --- 2 Liebert HPM --- A/W/F/D/H
Tab. 2 --- EC Fan Full setting
Model
UNDER (U) OVER (O) DISPLACEMENT (D) CONSTANT (K)
Std. Dehumidification Std. Dehumidification Std. Dehumidification Std. Dehum idification
VDC VDC VDC VDC VDC VDC VDC VD C
S0FxA/W
6.0 5.0 6.0 5.0 4.5 4.5 5.5 4.5
S0HxA/W
6.5 5.5 6.5 5.5 4.5 4.5 5.5 4.5
S1AxA/W
7.0 6.0 7.0 6.0 6.5 5.5 7.0 6.0
S1DxA/W
7.5 6.5 7.5 6.5 7.0 6.0 7.5 7.5
S1ExA/W
6.5 5.5 6.5 5.5 6.5 5.5 6.5 5.5
S1GxA/W
6.9 5.9 6.9 5.9 6.6 5.6 6.9 5.9
S2ExA/W
7.3 6.3 7.3 6.3 7.0 6.0 7.3 6.3
S2GxA/W
8.8 7.8 8.8 7.8 8.5 7.5 8.8 7.8
S1GxF/D/H
7.0 6.0 7.0 6.0
S2ExF/D/H
7.5 6.5 7.5 6.5
S2GxF/D/H
9.0 8.0 9.0 8.0
M2HxA/W
8.0 7.0 8.0 7.0 7.0 6.0 7.5 6.5
M3AxA/W
8.5 7.5 8.5 7.5 8.0 7.0
M3FxA/W
6.5 5.5 6.5 5.5
M3GxA/W
6.5 5.5 6.5 5.5
M4ExA/W
7.5 6.5 7.5 6.5
M4HxA/W
7.5 6.5 7.5 6.5
M5BxA/W
8.5 7.5 8.5 7.5
M5CxA/W
8.5 7.5 8.5 7.5
M5DxA/W
9.0 8.0 9.0 8.0
M7LxA/W
9.5 8.5 9.5 8.5
L8FUA/W
8.5 7.5
L9HUA/W
9.0 8.0
M2HxF/D/H
8.5 7.5 8.5 7.5
M3FxF/D/H
7.0 6.0 7.0 6.0
M3GxF/D/H
7.0 6.0 7.0 6.0
M4ExF/D/H
8.0 7.0 8.0 7.0
M4HxF/D/H
8.0 7.0 8.0 7.0
M5BxF/D/H
9.0 8.0 9.0 8.0
M5CxF/D/H
9.0 8.0 9.0 8.0
M5DxF/D/H
9.5 8.5 9.5 8.5
L8FxUF/D/H
8.5 7.5
NOTE:
The EC fan settings can be modified acting on the control display (see iCOM manual).