Vertiv | Liebert LVC | User Manual 5
Product Overview
1.3.3. Parameters of Operating Environment
Refer to Table 1-4 for parameters of operating environment
Table 1-4 Parameters of Operating Environment
Item Requirement
Installation position
The standard equivalent distance between the indoor unit and the condenser is 30m.
Vertical dierence* H: -5 ≤ H ≤ 20m. Installation mode vertical upward mode.
Ambient Temperature
Outdoor temperature -25 ~ + 45 °C. Low temperature accessories are required are
required if the temperature is between -35 °C~ + 20 °C
Operation Power 400V ± 10%, 50/60 Hz
Altitude ≤1000 m. Derating is required if the altitude exceed 1000m
Protection level Electrical control box and fan: IP55; Total unit; IPX5
Note*: - Indicates the condenser is above the indoor unit if the value is positive otherwise the value is negative.
When the equivalent distance between the indoor unit and the condenser exceeds 30m, refer to Sec-
tion 5.4.2- Refrigerant pipe equivalent length in “Liebert PEX Series Air Conditioner Technical Manu-
al” for the requirement of the equivalent length.
If the spray cooling module is installed in the condenser, it is advisable to drain-out water before
winter to avoid the frost cracking of spray cooling equipment.
1.3.4. Parameters of Storage Environment
Refer to Table 1-5 for parameters of storage environment
Table 1-5 Parameters of Storage Environment
Item Requirement
Storage environment Clean indoor environment with good ventilation and no dust
Ambient Temperature
-40 °C~ + 70 °C
Ambient relave humidity
5%RH ~ +70%RH
Storage time
Total transportation and storage time should not exceed six months, otherwise the
performance of the system need to re-calibrated.