Models
Figure # in Figure 10.1
above
Importance Factor Iρ= 1.0 Importance Factor Iρ= 1.5
Maximum Compressive
Reaction lb
Maximum Anchor
Maximum Compressive
Reaction lb
Maximum Anchor
Tensile
lb
Shear
lb
Tensile
lb
Shear
lb
Without
Receiver
Figure 1 37 14 14 47 24 21
With
Receiver
Figure 2 43 15 23 56 27 35
MCL055
Without
Receiver
Figure 1 37 14 14 47 24 21
With
Receiver
Figure 2 43 15 23 56 27 35
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
Table 10.1 Seismic anchorage loads for one-fan models (continued)