S600D
27
2.
Non-linear load (like switch power) affects the design of output and bypass neutral line. The neutral line current may exceed
the rated phase current, at most 1.5 times of the rated phase current.
Recommended CSA of UPS Cables and corresponding Lugs
The recommended CSA of the UPS cables is listed in Table 3-2.
Table 3-2 Recommended CSA of the UPS cable (unit: mm
2
, ambient temperature: 25°C)
When the system is in common input configuration and in 3-in 1-out mode, because phase A powers the load, the input cable of
phase A must be selected according to Table 3-2. Input cables of phase B and phase C may refer to Table 3-2.
Lugs for Input, Output, Common / Split Bypass, Battery connections MUST be of Ring type cross-section, suited for Cables and
Currents in use.
Selecting the UPS I/O Switch
Table 3-3 indicates the recommended UPS I/O switch capacity, the user may select it as required.
Table 3-3 Selecting the UPS I/O switch
Distance Between the UPS Connection Point and the Floor
See Table 3-4 for details.
Table 3-4 Min. distance between UPS connection point and floor
Notes
The following points are provided for general guidance only. If there are corresponding local regulations, such
regulations shall prevail.