EasyManua.ls Logo

Vertiv Liebert S600D - Electrical Specifications (Inverter Output); Electrical Specifications (Bypass Input)

Vertiv Liebert S600D
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S600D
96
10.6
Electrical Specifications (Inverter Output)
Table 10-6 Inverter output (to critical load)
Item
Unit
Rated power (kVA)
10kVA-20kVA
Rated AC voltage
1
Vac
220/230 (1-phase 2-wire, with neutral reference to the bypass neutral) (3-
in 1-out)
Frequency
2
Hz
50/60
Overload
%
For linear load requirements:
< 105%, continuous;
105 - 125% of rated load, 5min;
125 - 150% of rated load, 1min;
> 150%, 200ms
Non-linear load capacity
3
%
100%
Steady state voltage stability
%
±1% for balanced three phase load;
±2% for unbalanced load
Transient voltage response
4
%
±5% for 100% rated linear load step
Total harmonic voltage
%
2% (100% linear load);
5% (100% non-linear load)
Synchronisation window
Hz
Rated frequency ±0.5, ±1, ±2, ±3 (settable)
Slew rate (max. change rate of
synchronisation frequency)
Hz/s
Setting range: 0.2, 0.5, 1 (UPS module), 0.2 (parallel system)
1.
Factory set to 220V. 230V or 240V can be selected by service engineer at site.
2.
Factory set to 50Hz. 60Hz can be selected by service engineer at site. Note that the system frequency may only be changed
when the UPS is in bypass mode. It is strictly prohibited to change the system frequency when the UPS supplying the load via
the inverter.
3.
EN 50091-3 (1.4.58) crest factor 3:1, non-linear load.
4.
IEC/EN 62040-3/EN 50091-3 also for 0 - 100% - 0 load transient. Transient recovery time: returns to within 5% of steady state
output voltage within half a cycle.
10.7
Electrical Specifications (Bypass Input)
Table 10-7 Bypass input
Item
Unit
Rated power (kVA)
10kVA-20kVA
Rated AC voltage
1
Vac
220/230/240, 1-phase 2-wire, sharing neutral with the rectifier input and providing
neutral reference for the output, (3-in 1-out)
Overload
%
Based on nominal voltage and rated load current under apparent power:
< 105%, continues;
105 - 125% of rated load, 10min;
125 - 150% of rated load, 1min;
> 150%, 200ms
Frequency
2
Hz
50/60
Bypass voltage tolerance
%Vac
Upper limit: +10%, +15% or +20%, default: +20%;
Lower limit: -10%, -20%, -30% or -40%, default: -40%
Bypass frequency
tolerance
%
±5% or ±10%, default: ±10%
Synchronisation window
Hz
Rated frequency ±0.5, ±1, ±2, ±3, ±4, ±5 (settable); ±5 by default
1.
Factory set to 220V. 230V or V can be selected by service engineer at site.
2.
Factory set to 50Hz. 60Hz can be selected by service engineer at site.

Table of Contents