S600D
94
Chapter 10 Specifications
This section lists the UPS specifications.
10.1
Conformity and standards
The UPS has been designed to comply with the European and international standards listed in Table 10-1.
Table 10-1 European and international standards
Item
Reference Standards
General safety requirements for UPS
IEC/EN62040-1+A1:2013/AS62040-1
EMC requirements for UPS
IEC/EN62040-2:2006/AS62040-2
Method of specifying the performance and test requirements of UPS
IEC/EN62040-3/AS62040-3 (VFI SS 111)
The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series
and 60529).
10.2
Environmental Characteristics
Table 10-2 Environmental characteristics
Item
Unit
Rated power (kVA)
10kVA-20kVA
Noise at 1m (measured frontally)
dB (A)
58
Altitude
m
≤ 3000
Relative humidity
%RH
0 - 95%, non condensing
Operating temperature
°C
0 - 40°C (Note: Battery life is halved for every increase of 10°C above
20°C)
UPS storage temperature
°C
-25°C - +55°C
UPS shipping temperature
°C
-40°C - +70°C
10.3
Mechanical Specifications
Table 10-3 Mechanical specifications
Item
Unit
Rated power (10kVA-20kVA)
Standard UPS
Dimensions (W × D × H)
mm
335x650x1300
Net weight
mm
340(Approx)
Gross weight
kg
350(Approx)
Colour
kg
RAL7021
Protection rating, IEC (60529)
kg
IP20