Command Response Overview
This table summarizes the TL1 responses sent by the controller.
cr lf lf
^^^<source identifier>^<date>^<time> cr lf
M^^<ctag>^COMPLD[ cr lf
^^^"<response parameter blocks>"] cr lf;
<source identifier> is the system identifier
<ctag> is the <ctag> copied from the request
Request Verb
<response parameter blocks>
ACT-USER
/* This is a private computer system. cr lf
Unauthorized access may result in criminal prosecution */
CANC-USER
<null>
RTRV-ALM-
{ALL|EQPT}
Alarm details.
RTRV-EQPT
Controller part number, controller software version, etc.
RTRV-HDR
<null>
Autonomous Message Overview
This table summarizes the TL1 autonomous message sent by the controller.
cr lf lf
^^^<source identifier>^<date>^<time> cr lf
<almcde>^<atag>^verb[^modifier[^modifier] cr lf
<rspblk> + ;
<almcde> is the alarm code (*C for Critical Alarm, ** = Major Alarm, etc.)
<atag> is the autonomously generated ID (like a sequence number)
<rspblk> is the detailed information about the alarm; see details below.
Verb
<response parameter blocks>
REPT-ALM-EQPT
Alarm details.
CANCEL-SESSION