NetSure
™
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
NOT IMPLEMENTED AT THIS TIME
NOT IMPLEMENTED AT THIS TIME
Check why SMS modem failed.
SNMP configuration error.
Ambient Temp Summary Alarm
Ambient temperature alarm summary (one
or more alarms designated as ambient
temperature is active).
System current alarm active.
Check why system current alarm is active.
More than one rectifier has failed.
Check input voltage to rectifiers. Replace
rectifiers.
A rectifier cannot be detected by the
controller.
Reset the Rectifier Lost alarm. Replace
defective rectifier.
Rectifier Energy Optimization Mode is
enabled.
Check why system was placed into this
mode.
No response from all rectifiers.
Check the connectors and cables or the CAN
loop. Replace the controller.
If Energy Optimization Mode is enabled and
the controller oscillates in and out of Energy
Optimization more than 5 times, this alarm
is generated.
Check for other alarms.
Reset this alarm.
No AC input power to a rectifier.
Check why no AC input power available.
A rectifier has a high temperature condition.
Check why temperature is high.
A rectifier has a fault condition.
Refer to Rectifier User Manual for
troubleshooting information.
A rectifier has an overvoltage condition.
A rectifier is in protected mode.
A rectifier’s fan has failed.
A rectifier is in power limit.
Rectifier Communication Fail
A rectifier has lost communications with the
controller.
Check communications cables. Reset the
Communication Fail alarm. Replace the
rectifier.
A rectifier is in output power derating mode.
Refer to Rectifier User Manual for
troubleshooting information.
A rectifier has a current sharing alarm.
AC Under Voltage Protection
A rectifier is in under voltage protection
mode.
Rectifier alarm summary (one or more
alarms designated as rectifier is active).