A solar converter’s fan has failed.
A solar converter is in current limit.
Solar converter overload. The load is higher
than solar converter capacity. If one or more
of the solar converters are defective, replace
the faulty solar converters.
Solar Converter Comm Fail
A solar converter has lost communications
with the controller.
Check communications cables. Reset the
Solar Converter Communication Fail alarm.
Replace the solar converter.
A solar converter is in output power derating
mode.
Refer to Solar Converter User Manual for
troubleshooting information.
A solar converter has a current sharing
alarm.
Input Under Voltage Protection
A solar converter is in under voltage
protection mode.
Input to solar converter mounting position is
not DC.
Short Battery Test Running
Battery is in short time test mode.
Battery is in equalize charge test mode.
Battery is in manual battery discharge test
mode.
Battery is in planned battery test mode.
AC power has been switched off to the
rectifiers to perform a battery discharge
test.
Battery is in manual equalize charging
mode.
Battery is in automatic equalize charging
mode.
Battery is in cyclic equalize charging mode.
In Power Split mode, “System A” starts
equalize charging with the “System B”.
In Power Split mode, “System A” starts the
test with the “System B”.
Discharge Current Imbalance
Battery distribution current imbalance
alarm.
The currents from two groups of batteries
are not equal. Check the batteries.