Figure 3-21 Pull out the pump power plug
The pump power plug for different versions of VRC1 units is depicted as the table below.
Table3-1 Pump power plug
3.4.6 Connect the duct to the transition part
The total length of the cylindrical part of the transition part is 100 mm (3.94’’). To ensure the connection
reliability, the minimal overlapping of duct and transition part should not be less than 90 mm (3.54’’), and
make sure the clamping force is sufficient.
Figure 3-22 Connect the duct and transition part
NOTES:
• Before connecting the duct, the air duct needs to pass through the rear cabinet plinth firstly.