EasyManua.ls Logo

VESDA VESDA-E VEA - NFPA72 Code Compliance; NFPA72 Requirements

VESDA VESDA-E VEA
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VESDA-E VEA Commissioning Guide
4 32407_01
3 NFPA72 Code Compliance
3.1 NFPA72 Requirements
VESDA-E VEA is classified as an Aspirating Smoke Detection (ASD) product and it complies with NFPA72
Initial Acceptance and Annual testing requirements with minimal testing. With full supervision and automated
centralized tests, VEA verifies end to end system operation continuously and automatically performs system
integrity tests at set times and at much shorter intervals than the annual period required by NFPA72.
The below sections are taken from the NFPA72 2013 edition.
14.2.8 Automated Testing
14.2.8.1 Automated testing arrangements that provide equivalent means of testing devices to those specified
in Table 14.4.3.2 at a frequency at least equivalent to those specified in Table 14.4.3.2 shall be permitted to
be used to comply with the requirements of this chapter.
14.2.8.2 Failure of a device on an automated test shall result in an audible and visual trouble signal.
14.2.9 Performance-Based Inspection and Testing
As an alternate means of compliance, subject to the authority having jurisdiction, components and systems
shall be permitted to be inspected and tested under a performance-based program.
Explanation of VEA being an Air Sampling Detector (ASD):
So both ASD systems work exactly in the same way; the same rules apply to both the systems.
In addition:
VEA continuously monitors airflow from each sampling point to detect clogged/broken tubes or sample
points meeting NFPA72 Table 14.4.3.2 Air Sampling requirement of verification of airflow.
Full supervision of sampling port and microbore tube at set intervals much shorter than annual
requirement in NFPA72.
End to end system integrity monitoring allows centralized smoke test (to test smoke chamber) which
Xtralis recommends to test during commissioning and at the time of annual maintenance.

Other manuals for VESDA VESDA-E VEA

Related product manuals