7. Confirm that the alarm test ball valve (17) is closed.
8. Open the alarm line ball valve (16).
9. Confirm that there is no leakage from the intermediate valve cham-
ber. The restricted orifice/alarm line drain (18) should not be leak-
ing water or air.
10. Notify the authority having jurisdiction, remote station alarm moni-
tors, and those in the affected area that the valve is back in ser-
vice.
11. Provide test results to the authority having jurisdiction, if required.
WATER LEVEL AND LOW AIR ALARM TESTS
The authority having jurisdiction may have standards that require water
level and low air alarm tests on a more frequent basis than national
requirements. Verify these requirements by contacting the authority
having jurisdiction in the affected area.
NOTICE
If a Series 746-LPA Dry Accelerator is installed, make sure the
authority having jurisdiction is notified that the water level and
low air alarm tests are in progress. Failure to close the isolation
ball valve of the Series 746-LPA Dry Accelerator may cause the
valve to trip, resulting in a false alarm.
•
1. Notify the authority having jurisdiction, remote station alarm moni-
tors, and those in the affected area that the water level and low air
alarm tests will be performed.
2. If a Series 746-LPA Dry Accelerator (28) is installed, close the iso-
lation ball valve.
3. Close the water supply main control valve (2).
I-756LPA.VDS_18
FireLock
®
European Dry Valve Stations
SERIES 756
WITH SERIES 776 LOW-PRESSURE ACTUATOR
I-756LPA.VDS
INSTALLATION, MAINTENANCE, AND TESTING MANUAL
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_B