5726 783 PYROMAT DYN45 - DYN85 Issue 1.0 Page 45 of 72
Screen
number
Parameters Factory setting
05 Heating period 1, end:
Set switch-off time for the air heater.
L This setting is only available in day / off
operating mode.
22:00
06 – 23 Heating periods 2-7:
Dependant on the number of heating periods
(figure number 2), comprising heating days,
start and end.
-
24 Return temperature:
Desired return flow temperature
60°C
25 ECO mode:
The air heater is switched on and off depending
on requirement by the ECO economy-controller.
Yes
26 Switch-off under system temperature:
Should the air heater group be switched off
when the system temperature drops below a
minimum?
No
27 Frost protection function:
With the frost protection function switched on
the air heater will be switched on if there is a
danger of frost.
Yes
28 Excess heat take-off:
If there is a danger of the PYROMAT DYN
overheating, e.g. through too much fuel being
fed in by hand, then the excess heat can be
taken off if desired.
The air heater is controlled under "Maximum
flow temperature".
No