5726 783 PYROMAT DYN45 - DYN85 Issue 1.0 Page 49 of 72
Screen
number
Parameters Factory setting
38 Heating period 1, end:
Adjust end release of utility water heating.
L This setting is only available in timer
operating mode.
22:00
39 – 56 Heating periods 2-7:
Dependant on the number of heating periods
(figure number 35), comprising heating days,
start and end.
-
57 Utility water temperature:
Setting the desired utility water temperature.
60°C
6.5 Remote supply line
Function ECO-F
For an annex with a separate heat distribution system that is supplied with heat via a
remote supply line. The temperature of the remote supply line is pre-controlled for the
minimum pipeline loss, in accordance with the request of the heat distribution system.
Adjustable parameters
Screen
number
Parameters Factory setting
01 Heating - operating mode:
Operating mode selection.
Off
The pump is switched off, the valve is
closed.
Automatic
Control to required temperature.
Manual
The pump is switched on, the valve is not
controlled.
L Use this setting only for emergency
operation if a fault message is shown on the
display.
1. Inform your heating specialists for further
instructions on fault rectification.
automatic
02 Frost protection function:
With the frost protection function switched on
the remote supply line will be switched on if
there is a danger of frost.
Yes
03 Flow temperature, minimum:
Set the desired minimum temperature.
20°C
04 Flow temperature, maximum:
Maximum limit for flow temperature.
60°C