Page 50 of 72 PYROMAT DYN45 - DYN85 Issue 1.0 5726 783
6.6 Auxiliary heat generator
Heat generator function
single ECO-KE
An auxiliary heat generator is automatically switched in to cover the heat demand
(stand-alone) after the storage heat take-off.
Only the PYROMAT DYN can charge the storage. If this is put into operation then the
auxiliary heat generator switches off and the closed shut-off valve prevents it being
flooded through.
Single heat generator
flexible ECO-KG
An auxiliary heat generator is automatically switched in to cover the heat demand
(stand-alone) after the storage heat take-off.
Only the PYROMAT DYN can charge the storage. If this is put into operation then the
auxiliary heat generator switches off and the closed shut-off valve prevents it being
flooded through. The boiler temperature is controlled flexibly, commensurate with the
heat demand, to the minimum temperature.
Parallel heat generator
ECO-KP
An auxiliary heat generator is switched in automatically when required. This can be
done after the heat take-off of the storage in order to cover the complete heat demand
(stand-alone operation), or the auxiliary heat generator can serve to cover a spike in
heat demand (parallel operation to the PYROMAT DYN).
L For parallel operation a burner group is required for heat dissipation and this will
also serve to uphold the return line.
Adjustable parameters
Screen
number
Parameters Factory setting
01 Operating mode:
Operating mode selection.
Off
The auxiliary heat generator is switched off.
Automatic
Automatic enabling of the auxiliary heat
generator by the demand of a heat
consumer or (only ECO-KP) when the wood
burner temperature drops below a pre-
settable switch-in temperature.
On
The auxiliary heat generator is enabled.
Manual
The auxiliary heat generator is enabled and
(only ECO-KP) the pump is switched on, the
valve is not controlled.
L Use this setting only for emergency
operation if a fault message is shown on the
display.
1. Inform your heating specialists for further
instructions on fault rectification.
automatic