5726 783 PYROMAT DYN45 - DYN85 Issue 1.0 Page 51 of 72
Screen
number
Parameters Factory setting
02 Switch-on delay:
The release occurs after the time set has
elapsed.
15 minutes
03
Switch-on temperature system target
temperature:
If the system temperature drops below the
system target temperature by this value then the
switch-on delay (figure number 2) starts to run.
-15°C
04
Switch-off temperature system target
temperature:
Switch-off differential for parallel operation and
accumulator charging set to NO.
-5°C
05 Boiler flow, maximum: 80°C
06 Boiler flow, minimum: 20°C
07 Return temperature target:
Set target value for return temperature.
50°C
08 Load storage:
Should the storage be heated up by the auxiliary
heat generator?
No
09 Load storage to:
Up to which heat storage sensor should the
storage be loaded?
Storage top
10 Load storage to:
Up to which temperature on the selected
storage sensor should the auxiliary heat
generator heat the storage?
70°C
12 Service function, auxiliary heat generator
Maintenance function for specialists.
13 Operating hours counter, solar