Cylinder capacity l 160 200 300 500 750 1000
Length (7)
– Incl. thermal insulation a mm 581 581 633 859 960 1060
– Excl. thermal insulation mm — — — 650 750 850
Width
– Incl. thermal insulation b mm 608 608 705 923 1045 1145
– Excl. thermal insulation mm — — — 837 947 1047
Height
– Incl. thermal insulation c mm 1189 1409 1746 1948 2106 2166
– Excl. thermal insulation mm — — — 1844 2005 2060
Height when tilted
– Incl. thermal insulation mm 1260 1460 1792 — — —
– Excl. thermal insulation mm — — — 1860 2050 2100
Installation height mm — — — 2045 2190 2250
Weight incl. thermal insulation kg 86 97 151 181 295 367
Heating water capacity l 5.5 5.5 10.0 12.5 24.5 26.8
Heating surface
m
2
1.0 1.0 1.5 1.9 3.7 4.0
Connections (male thread)
Heating water flow and return R 1 1 1 1 1¼ 1¼
Cold water, DHW R ¾ ¾ 1 1¼ 1¼ 1¼
DHW circulation R ¾ ¾ 1 1 1¼ 1¼
Information regarding continuous output
When engineering systems with the specified or calculated continuous
output, select a matching circulation pump. The stated continuous out-
put is only achieved when the rated boiler heating output is ≥ the con-
tinuous output.
160 and 200 litre capacity
BÖ Inspection and cleaning aperture
E Drain
HR Heating water return
HV Heating water flow
KW Cold water
SPR Cylinder temperature sensor of the cylinder temperature con-
troller or thermostat
VA Protective magnesium anode
WW DHW
Z DHW circulation
DHW cylinder
(cont.)
38
PYROMAT ECO
6
5822 546 GB