Quieter operation Quieter operation of the outdoor unit: During quieter operation, the compressor
and fan are operated at reduced speed.
■
Function Enable/disable quieter operation.
■
Time program Set the time program for quieter operation: See operating instructions.
■
Adjustable by system
user
Enable whether the time program for quieter operation can be set by the system
user.
Screed drying If a profile is selected, screed drying begins with the respective temperature/time
profile, after the commissioning assistant finishes.
■
Not active Screed drying is not switched on.
■
Profile A Temperature/time profile 1 (in acc. with EN 1264-4)
t/d
ϑ
/°C
1 5 10 15 20 25 30
10
20
30
40
50
■
Profile B Temperature/time profile 2 (in acc. with ZV parquet and flooring technology)
t/d
ϑ
/°C
1 5 10 15 20 25 30
10
20
30
40
50
■
Profile C Temperature/time profile 3 (in acc. with Austrian Standards)
ϑ
/°C
t/d
1 5 10 15 20 25 30
10
20
30
40
50
■
Profile D Temperature/time profile 4
t/d
ϑ
/°C
1 5 10 15 20 25 30
10
20
30
40
50