EasyManua.ls Logo

Viessmann Vitocal 252-A Series - Page 168

Viessmann Vitocal 252-A Series
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
168
Measure Completed Comments
(
Repairs on sealed enclosures
When carrying out work on sealed components, fully isolate the
appliance from the power supply, also before removing sealed
covers.
If a power supply is absolutely necessary during the work: Posi-
tion a continuously operating refrigerant detector in the most
critical locations, to provide warning of any potentially danger-
ous situation.
Pay special attention to ensuring that any work on electrical
components does not lead to any changes to the enclosures
that would affect their protective properties. This includes dam-
age to leads, too many connections on a single terminal, con-
nections that do not correspond to the manufacturer's specifica-
tion, damage to seals, as well as incorrect installation of cable
entries.
Ensure the appliance is correctly installed.
Check that the seals have settled. Ensure by checking that the
seals reliably prevent the ingress of a flammable atmosphere.
Replace defective seals.
!
Please note
Silicone as a sealant can affect the function of leak detec-
tion devices.
Do not use silicone as a sealant.
Spare parts must correspond to the manufacturer's specifica-
tions.
Work on components which are suitable for flammable atmos-
pheres: It is not imperative that these components are isolated
from the power supply.
)
Repairs on components that are suitable for flammable at-
mospheres
Do not connect any continuous capacitive or inductive loads to
the appliance, unless it has been ensured that the permissible
voltages and currents are not exceeded.
In areas where flammable atmospheres exist, only apply voltage
to components which are suitable for flammable atmospheres.
Only use Viessmann original parts or parts approved by Viess-
mann. Other parts may result in refrigerant becoming ignited in
the event of a leak.
Wiring
Check whether the wiring is subject to wear, corrosion, tension,
vibration, sharp edges or other unfavourable environmental in-
fluences.
When checking, also take into account the effects of ageing and
continuous vibration on the compressor and fans.
aA
Refrigerant detectors
On no account use possible ignition sources for refrigerant de-
tection or leak detection.
Flame leak detectors or other detectors with open flames must
not be used.
Outdoor unit maintenance
Checklist for maintenance work (cont.)
6222080
Maintenance

Table of Contents

Related product manuals