Regulations to be observed
National installation regulations
Statutory regulations for the prevention
of accidents
Statutory regulations for environmental
protection
Statutory requirements for pressure
equipment:
Pressure Equipment Directive
2014/68/EU
Codes of practice of the relevant trade
associations
Relevant country-specific safety regu-
lations
Applicable regulations and guidelines
for operation, service, maintenance,
repair and safety of cooling, air condi-
tioning and heat pump systems con-
taining flammable and explosive refrig-
erant.
Safety instructions for working on the system
The outdoor unit contains flammable
refrigerant R290 (propane C3H8). If
there is a leak, the escaping refrigerant
may form a flammable or explosive
atmosphere in the ambient air. A safety
zone is defined in the immediate vicinity
of the outdoor unit, in which special
rules apply when working on the appli-
ance.
Working in the safety zone
Danger
Risk of explosion: Escaping refrig-
erant may form a flammable or
explosive atmosphere in the ambi-
ent air.
Take the following measures to pre-
vent fire and explosion in the safety
zone:
Keep ignition sources away, e.g. naked
flames, hot surfaces, electrical devices
not free of ignition sources, mobile
devices with integrated batteries (e.g.
mobile phones, fitness watches, etc.).
Permissible tools:
All tools for working in the safety zone
must be designed and explosion-pro-
tected in accordance with the applica-
ble standards and regulations for
refrigerant in safety group A3, e.g.
brushless machines (cordless screw-
drivers), extraction equipment, disposal
containers, installation aids, vacuum
pumps, conductive hoses, mechanical
tools of non-sparking material, etc.
Note
The tools must also be suitable for the
pressure ranges in use.
Tools must be in perfect maintenance
condition.
The electrical equipment must meet
the requirements for areas at risk of
explosion, zone 2.
Do not use flammable materials, e.g.
sprays or other flammable gases.
Discharge static: Before beginning
work, touch earthed objects, such as
heating or water pipes.