43
Emissions test mode for testing flue gas
with briefly raised boiler water tempera-
ture.
Emissions test mode should only be acti-
vated by your flue gas inspector during
the annual inspection.
Extended menu
1.
2. "Test mode"
Should the current flow rate be insuf-
ficient (only for boilers with flow
meters), the message "Check flow
rate" appears and symbol
Ñ
rotates.
Ensure adequate heat transfer (e.g.
open radiator valves).
3. "Activate?" "Yes"
"Flue gas test ON"
Test mode
Terminate with
OK
Boiler temperature 62°C
The following functions are activated:
■ The burner is switched on (the dis-
play shows ).
Note
Burner start-up can be delayed,
e.g. due to fuel oil preheating.
■ The pumps are started.
■ The mixers remain set to the control
function.
■ The temperature controller regu-
lates the boiler water temperature.
Note
The flue gas inspector can also activate
emissions test mode if the controls are
locked out by your heating contractor.
Emissions test mode
Emissions test mode
5592 682 GB