The Vitotwin 300-W auxiliary burner
remains blocked as long as there is an
adequate flow temperature from the
solid fuel boiler.
Cylinder temperature control
DHW heating begins when the cylinder
temperature is 2 K below the set cylinder
temperature and ends when the set cyl-
inder temperature is reached.
Both burners start with a time delay in the
delivered condition.
The enable criteria for both burners can
be changed via code 3213 to optimise
burner runtimes.
Setting options:
"No restrictions"
Same enable criteria as for central
heating.
"Eng bu only"
Only the Stirling burner is enabled for
DHW heating. The auxiliary burner is
only enabled in the event of a Stirling
burner fault.
"First charg eng bu only"
Only the Stirling burner is enabled for
the first DHW heating operation of the
day. The auxiliary burner is only ena-
bled in the event of a Stirling burner
fault.
Enable is unrestricted for any other
DHW heating operations during the
day.
"Fir'cha. eng bu, supp bu else"
Only the Stirling burner is enabled for
the first DHW heating operation of the
day. The auxiliary burner is only ena-
bled in the event of a Stirling burner
fault.
Only the auxiliary burner is enabled for
any other DHW heating operation dur-
ing the day (unless the Stirling burner
is already in operation).
Function description
Boiler temperature control
(cont.)
5618 294 GB