EasyManua.ls Logo

Viessmann Vitotwin 300-W - Specification

Viessmann Vitotwin 300-W
192 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
186
Rated voltage 230 V
Rated frequency 50 Hz
Rated current 6 A
Safety category I
IP rating IP X 4 D to
EN 60529
Permissible ambient temperature
during operation 0 to +40 °C
during storage and
transport -20 to +65 °C
Electronic tempera-
ture limiter setting 82 °C
Temperature limiter
setting 100 °C (fixed)
Backup fuse (power
supply) max. 16 A
Gas condensing boiler I
2ELL
Rated heating output range
T
V
/T
R
40/30 °C
kW 3.5 to 26
Rated heating output range
T
V
/T
R
75/60 °C
kW 3.2 to 24.6
Rated heat input range kW 3.6 to 25.2
Nominal electrical rating (max.) kW 1.0
Total elect. consumers (max.) W 138
Connection values
relative to the max. load
Natural gas E
m
3
/h
2.61
Natural gas LL
m
3
/h
3.11
Product ID
_-0085CM0150
Note
The connection values are only for doc-
umentation purposes (e.g. in the gas
contract application) or to estimate a
supplementary volumetric settings
check. Due to the factory settings, the
gas pressure must not be altered from
these values. Reference: 15 °C,
1013 mbar.
Specification
Specification
5618 294 GB

Table of Contents

Other manuals for Viessmann Vitotwin 300-W

Related product manuals