Installation Guide MX1 Fire Alarm System (NZ)
LT0360 ISSUE 2.43 29 NOVEMBER 2017 PAGE 25
MX1 Fire Alarm System – SPECIFICATIONS
590 x 480 x 140mm (H x W x D)
750 x 550 x 210mm (H x W x D)
Construction:
Slimline
15U
1.2mm mild steel, zinc coated. Baked epoxy powdercoat finish. 003 key
1.6mm mild steel, zinc coated. Baked epoxy powdercoat finish. 003 key
Shipping Weight:
Slimline
15U
12 kg approx., excluding batteries
24 kg approx., excluding batteries.
0 to +45C operating, up to 95% RH (non-condensing)
IP41 (Slimline), IP30 (15U)
Single phase 200-260VAC, 50-60Hz, 1.2A
27.3V, 5.0A DC charging, 5.5A DC current limit (nominal)
4.0A DC continuous long term Slimline model (FP0893)
5.0A DC continuous long term all other models.
Slimline holds 2 x 12V sealed lead-acid batteries, up to 17Ah capacity
(24Ah possible side-on). 15U cabinet holds up to 40Ah.
Three VBF and one VRZDU terminals (battery-backed) and one VNBF
(non battery-backed) terminal, wire capacity 2.5mm
2
. Each output is fused at 3A
(20 x 5 slow blow cartridge type).
Output loop current
Terminals
Up to 1.0A continuous. Overcurrent cutout at 1.1A (nominal).
AL+, AL-, AR+, AR-. Wire capacity 4.0mm
2
.
Output loop current
Loop Terminals
Power Terminals
Up to 1.0A continuous. Overcurrent cutout at 1.1A (nominal).
AL+, AL-, AR+, AR-. Wire capacity 4.0mm
2
.
+24V, 0V x 2. Wire capacity 4.0mm
2
.
Two protected supervised general purpose inputs suitable for connection to
contact or open collector outputs. EOLR value is 1.5k-3.3k.
Each relay provides a voltage-free set of changeover contacts, rated at 1A inductive
or 2A resistive at 30VDC. Configurable contact, load or door-holder mode supervision.
ANC1 has a demountable screw terminal header compatible with pre-made loom LM0319
to connect to a T-Gen2 or T-GEN 50 tone generator.
ANC2 has 2.5mm
2
capacity screw terminals.
A single set of voltage-free changeover contacts, 5A resistive at 30V. Negative bias
supervision of up to three branches of wiring is possible from this relay.
EOLR values are 9.1k for a single branch, 2 x 18k for a double branch and 3 x 27k
for a triple branch.
Two protected general purpose open collector 2.5mm
2
outputs which can be used to
drive loads of up to 500mA. Load mode supervision is optional on these outputs.
Male DB9 connector configured as DTE. For connection to PC for diagnostics,
programming, or firmware update. Requires null-modem cable, e.g., LM0076.
Can be connected to a modem for dial-in remote access. This requires a straight serial
cable.
Serial Port 1
Other Serial Ports
Male DB9 connector configured as DTE. Suitable for connection to a logging printer.
Requires null-modem cable for printer connection, e.g., LM0076.
Five 10 way headers configured as logic level (0-5V) DTE. Display Port is dedicated to the
LCD/Keyboard connection. Data rate is fixed at 19200 bps, 8 bits, no parity. Serial Port 0
by default is assigned to RZDU, but can be re-assigned to other functions. Serial ports 2, 3,
4 and 0 are configurable for MX Loop Cards, Remote FBP, or Network Interface.
Four 2.5mm
2
capacity screw terminals, for connection to up to 8 remote display devices
using proprietary RZDU protocol.
10 way FRC header suitable for connection to VIGILANT® GP SGD (PA0862) or GP
Brigade Relay Interface (PA0861).
Isolated and protected screw terminal, 4mm
2
capacity, for 2 wire connection to an ASE
FAS input. Transmits Alarm, Fault and Isolate. (Not currently used in NZ).
Three sets of voltage-free changeover contacts, rated at 1A inductive at 30V, with
2.5mm
2
capacity terminals, for Fire/Alarm, Defect/Fault, and Isolate/Disable signalling.