Examples Manual BG41/BG42/BG43
5-26 Rev. 99/49
Restart OB
OB21
BIB #6075
00000 :SPA FB 37
NAME #SYNCHRON
ADRE =KH F080 Base address
SSNR =KF +1 Interface number
BAUD =KF +10 Baud rate (9600)
FORM =KM 00000001 11111100 Parity even,2 Stop bits,8 bits per byte
PRIO =KF +0 Low transmission priority
BLOC =KF +64 Block size between SPS and the card
ZVZ =KF +20 Character delay time 200 ms
QVZ =KF +220 Acknowledgement delay time 2200 ms
PAFE =MB 199 Error byte
NEUS =M 0.0 New start flag
0000C :
0000D :SPA FB 37
NAME #SYNCHRON
ADRE =KH F080 Base address
SSNR =KF +2 Interface number
BAUD =KF +10 Baud rate (9600)
FORM =KM 00000001 11111100 Parity even,2 Stop bits,8 bits per byte
PRIO =KF +0 Low transmission priority
BLOC =KF +64 Block size between SPS and the card
ZVZ =KF +20 Character delay time 200 ms
QVZ =KF +220 Acknowledgement delay time 2200 ms
PAFE =MB 199 Error byte
NEUS =M 0.0 New start flag
00019 :
0001A :BE
Power On OB
OB22
BIB #6075
00000 :SPA FB 37
NAME #SYNCHRON
ADRE =KH F080 Base address
SSNR =KF +1 Interface number
BAUD =KF +10 Baud rate (9600)
FORM =KM 00000001 11111100 Parity even,2 Stop bits,8 bits per byte
PRIO =KF +0 Low transmission priority
BLOC =KF +64 Block size between SPS and the card
ZVZ =KF +20 Character delay time 200 ms
QVZ =KF +220 Acknowledgement delay time 2200 ms
PAFE =MB 199 Error byte
NEUS =M 0.0 New start flag
0000C :
0000D :UN M 0.0 Set the new start flag in order to
0000E :S M 0.0 block the building block in OB1
0000F :SPA FB 37
NAME #SYNCHRON
ADRE =KH F080 Base address
SSNR =KF +2 Interface number
BAUD =KF +10 Baud rate (9600)
FORM =KM 00000001 11111100 Parity even,2 Stop bits,8 bits per byte
PRIO =KF +0 Low transmission priority
BLOC =KF +64 Block size between SPS and the card
ZVZ =KF +20 Character delay time 200 ms
QVZ =KF +220 Acknowledgement delay time 2200 ms
PAFE =MB 199 Error byte
NEUS =M 0.0 New start flag
0001B :
0001C :BE