EasyManuals Logo

Vortice VORT HR 300 NETI Instruction Booklet

Vortice VORT HR 300 NETI
Go to English
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
DEUTSCH
120
12 Kommunikationsparameter
Aus dem Menü 23 ist es durch den Aufruf des Untermenüs "modbus" möglich, die folgenden Parameter in Bezug auf
RS485_2 zu ändern:
Slave Address: von 1 bis 254, standarmäßig 1
Baud Rate: 9600/19200, standarmäßig 19200
Parität: NONE
13 Befehle
Read Coil (Function Code = 01 )
Read Holding Registers (Function Code = 03 )
Read Input Register (Function Code = 04 )
Write Multiple Coils (Function Code =15 )
Write Multiple Holding Registers (Function Code = 16 )
14 Parameterübersicht
VARIABEL TYP ZULÄSSIGE WERTE READ/WRITE ADRESSE
ON/OFF BOOL TRUE, FALSE W/R 16399
FUNKTIONSGESCHWINDIGKEIT 16BIT-INT 1,2,3,4 W/R 16400
TEMPERATUR SOLLWERT 1
(SP1) BYPASS
16BIT-INT 15 ÷ 30 W/R
TEMPERATUR SOLLWERT 2
(SP2) POSTHEATER
16BIT-INT 10 ÷ 25 W/R 16401
GESCHWINDIG.1 SUPPLY (V1S) 16BIT-INT VMIN ÷ V2S W/R 16402
GESCHWINDIG.2 SUPPLY (V2S) 16BIT-INT V1S ÷ V3S W/R 16403
GESCHWINDIG.3 SUPPLY (V3S) 16BIT-INT V2S ÷ V4S W/R 16404
GESCHWINDIG.4 SUPPLY (V4S)
(FALLS VORHANDEN)
16BIT-INT V3S ÷ VMAX W/R 16405
ABGASSTUFE 1 (V1H) 16BIT-INT VMIN ÷ V2H W/R 16406
ABGASSTUFE 2 (V2H) 16BIT-INT V1H ÷ V3H W/R 16407
ABGASSTUFE 3 V3H) 16BIT-INT V2H ÷ V4H W/R 16408
ABGASSTUFE 4 (V4H) 16BIT-INT V3H ÷ VMAX W/R 16409
AKTIVIERUNG ZEITZONEN BOOL TRUE, FALSE W/R 16410
MINIMAL ZULÄSSIGEA
GESCHWINDIGKEIT (VMIN)
16BIT-INT 0 ÷ VMAX R 16411
MAXIMUM
PERMITTED SPEED (VMAX)
16BIT-INT VMIN ÷ 100 R 8961
RELATIVE LUFTFEUCHTIGK
HR%
16BIT-INT 0 ÷ 100 R 8964
LUFTQUALITÄT VOC 16BIT-INT 0 ÷ 100 R 8974
TEMPERATUR NTC 1 (INT) 16BIT-INT -40 ÷ 60 R 8976
TEMPERATUR NTC 2 (EST) 16BIT-INT -40 ÷ 60 R 8977
TEMPERATUR NTC 3 (EXH) 16BIT-INT -40 ÷ 60 R 8978
TEMPERATUR NTC 4 (SUP) 16BIT-INT -40 ÷ 60 R 8979
BYPASS AKTIV BOOL TRUE,FALSE R 8981
NOFROST AKTIV BOOL TRUE,FALSE R 8982
POSTHEATER AKTIV BOOL TRUE,FALSE R 8983
VORHANDENSEIN ALARME 16BIT-INT (*) R 8984

Table of Contents

Other manuals for Vortice VORT HR 300 NETI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vortice VORT HR 300 NETI and is the answer not in the manual?

Vortice VORT HR 300 NETI Specifications

General IconGeneral
BrandVortice
ModelVORT HR 300 NETI
CategoryHeating System
LanguageEnglish

Related product manuals