POLSKI
240
13 Polecenia
Read Coil (Function Code = 01)
Read Holding Registers (Function Code = 03)
Read Input Register (Function Code = 04)
Write Multiple Coils (Function Code =15)
Write Multiple Holding Registers (Function Code = 16)
14 Parameter map
ZMIENNA TYP DOZWOLONE WARTOŚCI READ/WRITE ADRES
ON/OFF BOOL TRUE, FALSE W/R 16399
OBECNOŚĆ ALARMÓW 1,2,3,4 W/R 16400
TEMPERATURA NASTAWY 1
(SP1) - BYPASS
OBECNOŚĆ ALARMÓW 15 ÷ 30 W/R
TEMPERATURA NASTAWY 2
(SP2) - POSTHEATER
OBECNOŚĆ ALARMÓW 10 ÷ 25 W/R 16401
OBECNOŚĆ ALARMÓW VMIN ÷ V2S W/R 16402
OBECNOŚĆ ALARMÓW V1S ÷ V3S W/R 16403
OBECNOŚĆ ALARMÓW V2S ÷ V4S W/R 16404
OBECNOŚĆ ALARMÓW V3S ÷ VMAX W/R 16405
OBECNOŚĆ ALARMÓW VMIN ÷ V2H W/R 16406
OBECNOŚĆ ALARMÓW V1H ÷ V3H W/R 16407
OBECNOŚĆ ALARMÓW V2H ÷ V4H W/R 16408
OBECNOŚĆ ALARMÓW V3H ÷ VMAX W/R 16409
AKTYWACJA ZAKRESÓW
CZASOWYCH
BOOL TRUE, FALSE W/R 16410
MINIMALNA DOPUSZCZALNA
OBECNOŚĆ ALARMÓW 0 ÷ VMAX R 16411
MAKSYMALNA DOPUSZCZALNA
OBECNOŚĆ ALARMÓW VMIN ÷ 100 R 8961
OBECNOŚĆ ALARMÓW 0 ÷ 100 R 8964
OBECNOŚĆ ALARMÓW 0 ÷ 100 R 8974
TEMPERATURA NTC 1 (WEWN) OBECNOŚĆ ALARMÓW -40 ÷ 60 R 8976
TEMPERATURA NTC 2 (ZEWN) OBECNOŚĆ ALARMÓW -40 ÷ 60 R 8977
TEMPERATURA NTC 3 (ZAS) OBECNOŚĆ ALARMÓW -40 ÷ 60 R 8978
OBECNOŚĆ ALARMÓW -40 ÷ 60 R 8979
BYPASS AKTYWNY BOOL TRUE,FALSE R 8981
NOFROST AKTYWNY BOOL TRUE,FALSE R 8982
POSTHEATER AKTYWNY BOOL TRUE,FALSE R 8983
OBECNOŚĆ ALARMÓW (*) R 8984
*) Zmienna „obecność alarmów” odnosi się do zmiennej WORD (16 bits), w której każdy pojedynczy bit sygnalizuje obecność
alarmu w następującej kolejności: