PORTUGUÊS
180
12 Parâmetros de comunicação
A partir do menu 23, entrando no submenu “modbus”, é possível modificar os seguintes parâmetros relativos ao RS485_2:
Slave Address: de 1 a 254, padrão 1
Baud Rate: 9600/19200, padrão 19200
Igualdade: NONE
13 Controles
Read Coil (Function Code = 01)
Read Holding Registers (Function Code = 03)
Read Input Register (Function Code = 04)
Write Multiple Coils (Function Code =15)
Write Multiple Holding Registers (Function Code = 16)
14 Mapa de parâmetros
VARIÁVEL TIPO
VALORES
PERMITIDOS
READ/WRITE DIREÇÃO
ON/OFF BOOL TRUE, FALSE W/R 16399
VELOCID. DE OPERAÇÃO 16BIT-INT 1,2,3,4 W/R 16400
TEMPERATURA SETPOINT 1
(SP1) - BYPASS
16BIT-INT 15 ÷ 30 W/R
TEMPERATURA SETPOINT 2
(SP2) - POSTHEATER
16BIT-INT 10 ÷ 25 W/R 16401
VELOCIDADE 1 SUPPLY (V1S) 16BIT-INT VMIN ÷ V2S W/R 16402
VELOCIDADE 2 SUPPLY (V2S) 16BIT-INT V1S ÷ V3S W/R 16403
VELOCIDADE 3 SUPPLY (V3S) 16BIT-INT V2S ÷ V4S W/R 16404
VELOCIDADE 4 SUPPLY (V4S)
(SIM EXISTE)
16BIT-INT V3S ÷ VMAX W/R 16405
VELOCIDADE 1 EXHAUST (V1H) 16BIT-INT VMIN ÷ V2H W/R 16406
VELOCIDADE 2 EXHAUST(V2H) 16BIT-INT V1H ÷ V3H W/R 16407
VELOCIDADE 3 EXHAUST (V3H) 16BIT-INT V2H ÷ V4H W/R 16408
VELOCIDADE 4 EXHAUST (V4H) 16BIT-INT V3H ÷ VMAX W/R 16409
ATIVAR ZONAS HORAS BOOL TRUE, FALSE W/R 16410
VELOCIDADE MÍNIMA
PERMITIDO (VMÍN)
16BIT-INT 0 ÷ VMAX R 16411
VELOCIDADE MÁXIMA
PERMITIDO (VMAX)
16BIT-INT VMIN ÷ 100 R 8961
UMIDADE RELATIVA HR% 16BIT-INT 0 ÷ 100 R 8964
QUALIDADE DO AR VOC 16BIT-INT 0 ÷ 100 R 8974
TEMPERATURA NTC 1 (INT) 16BIT-INT -40 ÷ 60 R 8976
TEMPERATURA NTC 2 (EST) 16BIT-INT -40 ÷ 60 R 8977
TEMPERATURA NTC 3 (EXH) 16BIT-INT -40 ÷ 60 R 8978
TEMPERATURA NTC 4 (SUP) 16BIT-INT -40 ÷ 60 R 8979
BYPASS ATIVADO BOOL TRUE, FALSE R 8981
NOFROST ATIVADO BOOL TRUE, FALSE R 8982
POSTHEATER ATIVADO BOOL TRUE, FALSE R 8983
PRESENÇA DE ALARMES 16BIT-INT (*) R 8984
*) A variável "presença de alarme" retorna uma variável WORD (16 bits) na qual cada bit indica a presença ou ausência de