FRANCAIS
90
12 Paramètres de communication
Depuis le menu 23, en entrant dans le sous-menu “modbus”, il est possible de modifier les paramètres suivants relatifs à
RS485_2 :
Slave Address : de 1 à 254, par défaut 1
Baud Rate: 9600/19200, par défaut 19200
Parité: AUCUNE
13 Commandes
Read Coil (Function Code = 01 )
Read Holding Registers (Function Code = 03 )
Read Input Register (Function Code = 04 )
Write Multiple Coils (Function Code =15 )
Write Multiple Holding Registers (Function Code = 16 )
14 Plan paramètres
VARIABLE TYPE
VALEURS
AUTORISÉES
READ/WRITE ADRESS
ON/OFF BOOL VRAI, FAUX W/R 16399
VITESSE DE FONCTIONNMENT 16BIT-INT 1,2,3,4 W/R 16400
TEMPÉRATURE SETPOINT 1
(SP1) BYPASS
16BIT-INT 15 ÷ 30 W/R
TEMPÉRATURE SETPOINT 2
(SP2) POSTHEATER
16BIT-INT 10 ÷ 25 W/R 16401
VITESSE 1 SUPPLY (V1S) 16BIT-INT VMIN ÷ V2S W/R 16402
VITESSE 2 SUPPLY (V2S) 16BIT-INT V1S ÷ V3S W/R 16403
VITESSE 3 SUPPLY ((V3S) 16BIT-INT V2S ÷ V4S W/R 16404
VITESSE 4 SUPPLY ((V4S)
(SI EXISTANTE)
16BIT-INT V3S ÷ VMAX W/R 16405
VITESSE 1 EXHAUST (V1H) 16BIT-INT VMIN ÷ V2H W/R 16406
VITESSE 2 EXHAUST (V2H) 16BIT-INT V1H ÷ V3H W/R 16407
VITESSE 3 EXHAUST (V3H) 16BIT-INT V2H ÷ V4H W/R 16408
VITESSE 4 EXHAUST (V4H) 16BIT-INT V3H ÷ VMAX W/R 16409
AUTORISATION PLAGES
HORAIRES
BOOL VRAI, FAUX W/R 16410
VITESSE MINIMUM
PERMISE (VMIN)
16BIT-INT 0 ÷ VMAX R 16411
VITESSE MAXIMUM
PERMISE (VMAX)
16BIT-INT VMIN ÷ 100 R 8961
HUMIDITÉ RELATIVE HR% 16BIT-INT 0 ÷ 100 R 8964
QUALITÉ AIR VOC 16BIT-INT 0 ÷ 100 R 8974
TEMPÉRATURE NTC 1 (INT) 16BIT-INT -40 ÷ 60 R 8976
TEMPÉRATURE NTC 2 (EST) 16BIT-INT -40 ÷ 60 R 8977
TEMPÉRATURE NTC 3 (EXH) 16BIT-INT -40 ÷ 60 R 8978
TEMPÉRATURE NTC 4 (SUP) 16BIT-INT -40 ÷ 60 R 8979
BYPASS ACTIVÉ BOOL VRAI, FAUX R 8981
NOFROST ACTIVÉ BOOL VRAI, FAUX R 8982
POSTHEATER ACTIVÉ BOOL VRAI, FAUX R 8983
PRÉSENCE ALARMES 16BIT-INT (*) R 8984

Table of Contents

Other manuals for Vortice VORT HR 300 NETI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vortice VORT HR 300 NETI and is the answer not in the manual?

Vortice VORT HR 300 NETI Specifications

General IconGeneral
BrandVortice
ModelVORT HR 300 NETI
CategoryHeating System
LanguageEnglish

Related product manuals