Watlow EZ-ZONE
®
PM Integrated Controller • 83 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[Map]
[ Map]
Communications (1)
Data Map
If set to 1 the control
will use PM legacy
mapping. If set to
2 the control will
use new mapping to
accommodate new
functions.
1 to 2 1 if 9
th
digit
of part
number
is a D or
1 other-
wise, 2.
Always - - - - - - - - - - - - - - - -
[`nU;S]
[ nV.S]
Communications (1)
Non-volatile Save
If set to Yes all val-
ues written to the
control will be saved
in EEPROM.
[`yes] Yes (106)
[``no] No (59)
Yes Always Instance 1
Map 1 Map 2
2494 2974
0x96 (150)
1
8
198 uint
RWE
[`Ad;d]
[ Ad.d]
Communications (2)
DeviceNet™ Node
Address
Set the DeviceNet™
address for this gate-
wa y.
0 to 63
63 Always if
digit 8 is a
"5".
- - - - - - - - - - - - - - - -
[bAUd]
[bAUd]
Communications (2)
Baud Rate Devi-
ceNet™
Set the DeviceNet
speed for this gate-
way's communica-
tions to match the
speed of the serial
network.
[`125] 125 kb (1351)
[`250] 250 kb (1352)
[`500] 500 kb (1353)
125 Always if
digit 8 is a
"5".
- - - - - - - - - - - - - - - -
[`FC;E]
[ FC.E]
Communications (2)
DeviceNet™ Quick
Connect Enable
Allows for immediate
communication with
the scanner upon
power up.
[``no] No (59)
[`YES} Yes (106)
No Always if
digit 8 is a
"5".
- - - - - - - - - - - - - - - -
[P;Add]
[P.Add]
Communications (2)
Profibus Node Ad-
dress
Set the Profibus ad-
dress for this control.
0 to 126
126 Always if
digit 8 is a
"6".
- - - - - - - - - - - - - - - -
[a;loc]
[A.Loc]
Communications (2)
Profibus Address
Lock
When set to yes will
not allow address
to be changed using
software. Can be
changed from front
panel.
[``no] No (59)
[`YES} Yes (106)
No Always if
digit 8 is a
"6".
- - - - - - - - - - - - - - - -
[iP;M]
[iP.M]
Communications (2)
IP Address Mode
Select DHCP to let a
DHCP server assign
an address to this
module.
[dhCP] DHCP (1281)
[F;Add] Fixed Address (1284)
DHCP Always if
digit 8 is a
"3".
- - - - - - - - - - - - - - - -
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only