Watlow Series SD 78 Chapter 1 OverviewWatlow Series SD 78 Appendix
Without contact suppression
Minimum load current: 10 mA rms
Maximum current: 0.5A rms at 24 to 240VÅ (ac), resistive
20 VA pilot duty, 120/240VÅ (ac), inductive
Must use RC suppression for inductive loads
Maximum offstate leakage current: 100 µA rms
Electromechanical Relay, Form A
Minimum load current: 10 mA
2 A @ 240VÅ (ac) or 30VÎ (dc) maximum, resistive
125 VA pilot duty, 120/240VÅ (ac), inductive
Must use RC suppression for inductive loads
Electrical life 100,000 cycles at rated current
Electromechanical Relay, Form C
Minimum load current: 10 mA
5 A @ 240VÅ (ac) or 30VÎ (dc) maximum, resistive
125 VA pilot duty, 120/240VÅ (ac), inductive
Must use RC suppression for inductive loads
Electrical life 100,000 cycles at rated current
Process *
Range selectable: 0 to 20 mA, 4 to 20 mA, 0 to 5VÎ (dc), 1 to 5VÎ
(dc), 0 to 10VÎ (dc)
Reverse or direct acting
0 to 10VÎ (dc) voltage output into 1,000  minimum load resis-
tance
0 to 20 mA current output into 800  maximum load resistance
• Resolution:
dc ranges: 2.5 mV nominal
mA ranges: 5 µA nominal
• Calibration accuracy:
dc ranges: ±15 mV
mA ranges: ±30 µA
Temperature stability: 100 ppm/°C
Communications
EIA/TIA-485
• Isolated
Modbus™ RTU protocol
9600, 19200 and 38400 baud rates
A maximum of 32 units can be connected (with additional 485
repeater hardware, up to 247 units may be connected)
Sampling rate: 20 Hz
IrDA
Modbus™ RTU via IRCOMM over IrDA
Sampling rate: 20 Hz
Agency Approvals
UL Listed Process Control UL3121® (UL 61010C-1), c-UL, IP65
(NEMA 4X). File # E185611.
UL® is a registered trademark of the Underwriter’s Laborato-
ries, Inc.
CE approved. See Declaration of Conformity.
CSA approved C22.2#24, File 158031
NSF 2 approved for type E, J, K, T and RTD sensors,
File 49660-0002-000.
Terminals
• Touch-safe
Input power and control outputs: 0.2 to 4 mm2 (22 to 12 AWG),
6 mm (0.25 in) strip length
Sensor inputs and process outputs: 0.1 to 0.5 mm2 (28 to 20
AWG), 8 mm (0.30 in) strip length
Solid or tinned wire recommended for spring clamp style
connectors.
Torque: terminal blocks 1 to 6 (SD _ _ - _ [C, K or J] _ _ - _ _ _ _)
and 1 to 4 (SD _ _ - _ F _ _ - _ _ _ _ ) are 0.8 Nm (7 in-lb); termi-
nal blocks 12, 13, and 14 are 0.9 Nm (8 in-lb).
Power
100 to 240VÅ (ac) +10%; -15%; 50/60 Hz, ±5%
• 24V (ac/dc) +10%; -15%; 50/60 Hz, ±5%; Class 2 power source is
required for low-voltage model.
10VA maximum power consumption
Data retention upon power failure via nonvolatile memory
Operating Environment
-18 to 65°C (0 to 149°F)
0 to 90% RH, non-condensing
Storage temperature: -40 to 85°C (-40 to 185°F)
Dimensions
DIN Size
Behind
Panel
(max.)
Width Height
Display
Height
(in.)
1/32
97.8 mm
(3.85 in)
52.6 mm
(2.07 in)
29.7 mm
(1.17 in)
L — 7.6 mm (0.30)
R — 5.6 mm (0.22)
1/16
97.8 mm
(2.05 in)
52.1 mm
(3.85 in)
52.1 mm
(2.05 in)
U — 10.2 mm (0.40)
L — 6.1 mm (0.24)
1/8
Vertical
97.8 mm
(3.85 in)
52.8 mm
(2.08 in)
99.8 mm
(3.93 in)
U — 10.2 mm (0.40)
L — 6.1 mm (0.24)
1/8
Horizontal
97.8 mm
(3.85 in)
99.8 mm
(3.93 in)
52.8 mm
(2.08 in)
U — 10.2 mm (0.40)
L — 6.1 mm (0.24)
1 /4
101.1 mm
(3.98 in)
99.8 mm
(3.93 in)
99.8 mm
(3.93 in)
U — 14.2 mm (0.56)
L — 10.2 mm (0.40)
Weight (approximate)
SD3 - 75 g (0.16 lbs)
SD6 - 100 g (0.22 lbs)
SD8 - 145 g (0.32 lbs)
SD4 - 200 g (0.43 lbs)
Functionality Matrix
Universal
Input
Control Alarm Process
485
Comm
Input 1
Output 1
Output 2
Output 3
Note: These specifications are subject to change without prior
notice.

Related product manuals