Section 3 Auto-Zone Plus
3-46 Programming
Wetbulb Setpoints
WB Setpoints
Calibration Offset
Outdoor Air..: 77.1
Cal. Offset..: 0.0
The only setpoint available for this unit is the Calibration
Offset for the Thermistor Outdoor Air Temperature Sensor. If
location or other factors are causing the Outdoor Air
Temperature reading to be incorrect, the user can adjust the
reading up or down with this offset. Line 2 shows the current
temperature when you first enter this screen but it is not
dynamically updated after the offset is changed. You will need
to exit this screen, then return to this screen to see the effect of
the entered offset.
Minimum Default Maximum
Cal. Offset -100.0°F 0.0°F 100.0°F