EasyManua.ls Logo

WattMaster Auto-Zone Plus - Page 134

Default Icon
180 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 4 Auto-Zone Plus
4-16 Start-Up and Troubleshooting
1.3.7 Checking the Local Loop at the Zone Manager
Diagram
Meter Set To Read DC Volts
The indicated values are typical of a normal system. Actual readings may deviate slightly
due to the number of units connected and other system specific factors
Note: These tests assume that the controllers being checked are powered up.
Overvie
w
This is a “quick check” to determine if any of the Zone Controllers or CV Units on a Local
Communications Loop are damaged. Since all Zone Controllers and CV Units will “float”
both of their communications connections at about 2.45 Volts, you can quickly check an
entire loop by unplugging it at the Zone Manager.
Note: Be sure that the loop you are testing does not have a short circuit from T - R.
Damage typically occurs when the communications loop is exposed to excessive voltage, as
may occur during installation, due to wiring errors. The driver chips are socketed on all
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur due to wiring related problems.
Measurements
Local Loop Acceptable Range
T – SHLD 2.4 - 2.5 Volts DC
R – SHLD 2.4 - 2.5 Volts DC
Note Minor variances may not indicate a problem if both tests indicate similar values.
firealarmresources.com

Table of Contents

Related product manuals