Setup via IO-Link
Function Possible Settings Default
Temperature
mode
The sensor has internal temperature compensation. Alternatively, the
temperature can be measured externally and sent to the sensor as a
process or parameter.
Internal
Sensor operates with internal temperature compensation
External
Sensor works with external temperature compensation and uses the
transmitted process or parameters (see section “8.2 Condition Monitor-
ing/Process Data”). Whether process or parameter data is to be used is
specified via the setting under "Measured value unit "Process data type".
Internal
External
temperature
Temperature values can be transmitted to the sensor at a resolution of
1 °C for temperature compensation. Parameter is used if the external
temperature compensation is to work via the parameters.
–30…+60 °C
NOTE!
Regular updating of external temperature data is
recommended, in order to prevent abrupt temperature
changes and jumps in measurement results resulting
therefrom. If no temperature value is transmitted when
the sensor is started up in the external temperature
mode, the standard value of 23 °C is used.
23 °C