Commissioning en
Installation and operating instructions Wilo-Stratos PICO 17
If required, an offset value between 80% and 170% of the de-
termined setpoint can be set via the operating button in the
pump’s home screen.
The standard value is 100%.
Manual setting
The manual setting allows the regulation mode and the setpoint to be set manually.
Control mode
Dynamic Adapt plus (factory setting)
The control mode Dynamic Adapt plus with automatic setpoint
calculation autonomously adjusts the pump output to the re-
quirements of the system. A setpoint adjustment is not required.
The delivery rate of the pump is continuously adjusted to the de-
mand of the consumers and the state of open and closed valves.
This significantly reduces the pump energy used.
NOTICE
When Dynamic Adapt plus is activated, no setpoint adjustment is possible.
Variable differential pressure (Δp-v)
The pump reduces the delivery head by half when the volume
flow in the pipe network decreases.
This results in savings of electrical energy by adapting the deliv-
ery head to the volume flow requirement and lower flow rates.
Recommended for two-pipe heating systems with radiators to
reduce the flow noise at thermostatic valves.
NOTICE
Enter the value to be read from the characteristic curve as the setpoint, not the cal-
culated value.
Constant differential pressure (Δp-c)