ID57 OverTempFault_BAT The battery temp is too high
Please make sure WKS I inverter is installed in a
place without direct sunlight.
Please make sure WKS I inverter is installed in a
cool / well-ventilated place.
Make sure the inverter is vertically installed & the
ambient temperature is less than the temperature
upper limit of WKS I inverter
ID58
OverTempFault_
HeatSink
The temperature of heat
sink is too high
ID59 OverTempFault_Env
The environment temp is
too high
ID60
PE connectFault
Check the grounding of AC output PE wire.
ID65 unrecoverHwAcOCP
The grid current is too high
and has cause unrecoverable
hardware fault
ID65-ID67 are internal faults of WKS I inverter,
switch OFF WKS I inverter, wait for 5 minutes,
then switch ON WKS I inverter. Check whether
the problem is solved.
If no, please contact WATTUNEED technical support.
ID66 unrecoverBusOVP
The bus voltage is too high
and has cause unrecoverable
fault
ID67
BitEPSunrecover
BatOcP
Unrecoverable fault of
battery overcurrent in EPS
mode
ID68
UnrecoverIpv
Unbalance
The input current is
unbalance, and has
triggered unrecoverable
fault
Check the
PV input mode (parallel mode/
independent mode) setting of WKS I inverter. If
it’s incorrect, change the
PV input mode.
ID70 unrecoverOCPInstant
The grid current is too high,
and has cause unrecoverable
fault
ID70-ID73 are internal faults of WKS I inverter,
switch OFF WKS I inverter, wait for 5 minutes,
then switch ON WKS I inverter. Check whether
the problem is solved.
If no, please contact WATTUNNED
technical support.
ID73 UnrecoverIPVInstant
The input current is too high,
and has triggered
unrecoverable fault
ID74
UnrecoverPvConfigSet
Wrong
Incorrect input mode
Check the
PV input mode (parallel mode/
independent mode) setting of WKS I inverter. If
it’s incorrect, change the
PV input mode.
ID75 unrecoverEEPROM_W
Unrecoverable EEPROM
write
ID75-ID77 are internal faults of WKS I inverter,
switch OFF WKS I inverter, wait for 5 minutes,
then switch ON WKS I inverter. Check whether
the problem is solved.
If no, please contact WATTUNEED technical support.
ID76 unrecoverEEPROM_R Unrecoverable EEPROM read
ID77 unrecoverRelayFail
Relay has triggered
permanent fault
ID81 Over temperature
Internal temperature is too
high.
Please make sure WKS I inverter is installed in a
place without direct sunlight.
Please make sure WKS I inverter is installed in a
cool / well-ventilated place.
Make sure the inverter is vertically installed & the