EasyManua.ls Logo

Wolf FGB-35 - Technical Parameters According to EU Regulation No. 813;2013

Wolf FGB-35
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
102
3064458_201811
37. Technical parameters according to
EU regulation no. 813/2013
Type FGB-28 FGB-K-28 FGB-35 FGB-K-35
Condensing boiler [yes/no] yes yes yes yes
Low temperature boiler (**) [yes/no] no no no no
B11 boiler [yes/no] no no no no
Cogeneration space heater [yes/no] no no no no
If yes, equipped with a supple-
mentary heater
[yes/no] - - - -
Combination heater [yes/no] no yes no yes
Item Symbol Unit
Rated heat output P
rated
kW 24 24 31 31
Useful heat output at rated heat
output and high-temperature
regime (*)
P
4
kW 24.4 24.4 31.1 31.1
Useful heat output at 30% of
rated heat output and low-
temperature regime (**)
P
1
kW 7.3 7.3 9.3 9.3
Auxiliary electricity consumption
at full load
elmax kW 0.042 0.042 0.054 0.054
Auxiliary electricity consumption
at part load
elmin kW 0.015 0.015 0.016 0.016
Auxiliary electricity consumption
in standby mode
P
SB
kW 0.002 0.002 0.002 0.002
Seasonal space heating energy
efciency
n
s
% 93 93 93 93
Useful efciency at rated heat
output and high-temperature
regime (*)
n
4
% 87.9 87.9 87.4 87.4
Useful efciency at 30% of rated
heat output and low-temperature
regime (**)
n
1
% 98.1 98.1 98.1 98.1
Standby heat loss P
stby
kW 0.052 0.052 0.060 0.060
Ignition burner power consump-
tion
P
ing
kW 0.000 0.000 0.000 0.000
Emissions of nitrogen oxides NO
x
mg/kWh 26 26 26 26
Declared load prole (M,L,XL,XXL) - XL - XL
Daily electricity consumption Q
elec
kWh - 0.230 - 0.224
Water heating energy efciency
nwh
% - 84 - 84
Daily fuel consumption
Qfuel
kWh - 22.947 - 23.116
Contact details Wolf GmbH, Industriestrasse 1, D-84048 Mainburg
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
(**) Low temperature means 30 °C for condensing boilers, 37 °C for low-temperature boilers and for 50 °C return temperature (at heater inlet) other heaters.