eq
uired to install and service the boiler
within an airing cupboard.
5: VENTING COMPARTMENTS:
If the clearances are less than those stated
for options '3' & '4' (above) then ventilation
must be provided as described in BS 5440.
A minimum of 2 air vents (C) of equal size
must be fitted,
one at low
level and
another
at high level onto
t
he same
wall using the
same air for
circulation.
Minimum free area required for vent
ing
:
For air directly from outside:
FS 30CDi 155cm
2
FS 42CDi 217cm
2
For air from inter
nal space/r
oom:
FS 30CDi 310cm
2
FS 30CDi 433cm
2
100mm
6: BATHROOMS:
IMPORTANT:
Any switch or appliance control using mains
electricity must not be within reach of a
person using the bath or shower.
Electrical switches, fused spurs and socket
outlets must not be situated in the bathroom.
This boiler is IP X4 rated and can be installed
in zone 2, however where possible positions
outside zone 2 should be sought.
Additional RCD (Residual Current Device)
protection may be required.
Refer to the latest IEE wiring regulations.