Specifications and Characteristics
Output Performance Specifications
Release 3.0 239
30 Minute Drift
1
8 Hour Drift Temperature Stability
2
Temperature Coefficients
Analog Programming Interface
Voltage 0.04% of Vmax
Current 0.6% of Imax
Power 6000W: 1% of Pmax
12000W: 2% of
Pmax
1. At 25°C ±5°C, with full power load
Voltage 0.02% of Vmax
Current 6000W: 0.04% of Imax
12000W: 0.05% of imax
12000W 600V model: 0.08% of Imax
Power 0.1% of Pmax
2. At 25°C ±5°C after 30 minutes full load operation
Front Panel or Remote Digital Interface
Voltage Programming
Current Programming
Power Programming
Voltage Readback
Current Readback
Power Readback
0.04% of Vmax
/°C
0.06% of Imax/°C
0.1% of Pmax/°C
0.04% of Vmax/°C
0.06% of Imax/°C
0.1% of Pmax/°C
Remote Analog Programming Interface
Voltage Programming
Current Programming
Voltage Readback
Current Readback
0.04% of Vmax
/°C
0.06% of Imax/°C
0.04% of Vmax/°C
0.06% of Imax/°C
Programming Lines, Impedance
0-5 V
dc
range
0-10 V
dc
range
>30 kOhm
>30 kOhm
Readback Lines, Impedance
0-5 V
dc
range
0-10 V
dc
range
<500 Ohm
<1 kOhm
Isolation, all program and readback lines
300 Vdc with respect to chassis potential or negative output