Xinje VB3 - Close-loop Control Parameters (Group P7)

Xinje VB3
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
V5 series inverter
46
P6.07 First 2 times fault records First 2 times fault records 1 0 *
P6.08 First 3 times fault records First 3 times fault records 1 0 *
P6.09 First 4 times fault records First 4 times fault records 1 0 *
P6.10 First 5 times fault records First 5 times fault records 1 0 *
P6.11 First 6 times fault records First 6 times fault records 1 0 *
8. Close-loop control parameters (Group P7)
Group P7: Close-loop control parameters
Parameter Name Range
Minmum
unit
Default
setting
Change
P7.00
Close-loop function selection
0: Disabled
1: Enabled
1 0 ×
P7.01 Channel selection 0: Digital input
1: VI (0~10V) analog voltage
2: CI analog
1 1 ○
P7.02 Feedback channel selection 0: VI (0~10V) voltage input
1: CI analog input
2: VI+CI
3: VI-CI
4: Min{VI, CI}
5: Max {VI, CI}
1 1 ○
P7.03 Appointetd channel filter 0.01~50.00s 0.01s 0.50s ○
P7.04 Feedback channel filter 0.01~50.00s 0.01s 0.50s ○
P7.05 Digital setting 0.00~10.00V 0.01V 0.00V ○
P7.06 Min setting value 0.0~Max P7.08 0.1% 0.0% ○
P7.07 Feedback value corresponding to
min setting value
0.0~100.0% 0.1% 0.0% ○
P7.08 Max setting value Min P7.06~100.0% 0.1% 100.0% ○
P7.09 Feedback value corresponding to
max setting value
0.0~100.0% 0.1% 100.0% ○
P7.10 Proportional KP 0.000~9.999 0.001 0.050 ○
P7.11 Integral KI 0.001~9.999 0.001 0.050 ○
P7.12 Sampling cycle T 0.01~10.00S 0.01 1.00 ○
P7.13 Limits of deviation 0.0~20.0% 1% 2.0% ○
P7.14 Close loop adjustment characte-
ristic
0: Forward
1: Reverse
Note: relationship between setting value and speed
1 0 ×
P7.15 Integral adjustment selection
0: Stop integral adjustment when the frequency
reaches upper limit or lower limit
1: Continue the integral adjustment when the fre-
quency reaches high limit or lower limit
1 0 ×
P7.16 Close loop preset frequency 0~upper limit of of frequency 0.01Hz 0.00Hz ○
P7.17
Holding time of close-loop preset
frequency
0.0~250.0s
0.1s 0.1s ×
P7.18 Awakening threshold 0.00~500.00Hz 0.01Hz 0.01Hz ×
P7.19 backlash of zero-frequency 0.00~500.00Hz 0.01Hz 0.01Hz ×